Appendix D: SNMP MIBS
ManageUPSNET User Instruction Manual 49
Table 7. RFC1628 Support
upsIdent Group
upsIdentManufacturer US Manufacturer
upsIdentModel The model designation of the UPS
upsIdentUPSSoftwareVersion xx.x format (x = 0 to 9)
upsIdentAgentSoftwareVersion xx.xx format (x = 0 to 9)
upsIdentName. Default: Not set (upsIdentName)
upsIdentAttachedDevices Default: Not set(upsIdentAttachedDevices)
upsBattery Group
upsBatteryStatus The status of the UPS battery
upsSecondsOnBattery Normally 0. Increments for each second the UPS is on battery.
upsEstimatedMinutesRemaining This object is more meaningful when the UPS is operating on
battery. It is conservatively implemented, meaning that you should
have at least as many minutes remaining as indicated, if not more.
upsEstimatedChargeRemaining This object indicates remaining battery charge.
upsBatteryVoltage This object is normally used by trained personnel. The status of
the UPS battery is indicated by other objects, relieving users from
interpreting this object.
upsBatteryCurrent
upsBatteryTemperature Elevated operating temperatures impact battery life. If the
temperature is greater than 14°C (113°F), airflow to the UPS is
probably restricted.
upsInput Group
upsInputLineBads This counter increments when the UPS switches to battery. It does
not increment when an SNMP or serial command request forces
the UPS on battery.
upsInputNumLines. Number of phases. This is one for single phase UPS’s.
upsInputTable
upsInputFrequency Measured average.
upsInputVoltage True RMS voltage measurement.
upsInputCurrent The present input current.
upsInputTruePower Represents actual input watts.